135 Downloads
DESCRIPTION
The Fike Zone Interface Module, P/N 55-055/55-060, is used with CyberCat® intelligent control panels as an interface between the control panel and two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. IDC wiring may be connected in Class A or B configurations. All two-wire detectors being monitored must be UL compatible with this module. Refer to Fike’s two wire detector compatibility document P/N 06-467 for compatible list of detectors. This module supervises the zone of detectors and the connection to the control panel. There is a LED indicator on the module to indicate current status of the device. The isolator version of interface module, P/N 55-060, provides complete short circuit isolation for NFPA 72, Class X wiring.
APPROVALS
• UL - S3217
• FM
• CSFM- 7300-0900:0150
SPECIFICATIONS
Normal Operating Voltage: 15 to 30 VDC
Maximum Red LED Current Draw: 1.6 mA
Average Operating Current: 500 μA (LED flashing, 30 VDC, continuous broadcasts)
Maximum Alarm Current: 2.1 mA
EOL Resistance: 3.9K Ohms
Maximum IDC wiring resistance: 25 Ohms
IDC Supply Voltage (between terminals T7 and T8)
Regulated DC Voltage: 24 VDC power limited
Ripple Voltage: 0.1 Volts RMS maximum
Current: 90mA per module*
Temperature Range: 32 to 120°F (0 to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.5”H x 4”W x 1.25”D (114mm H x 102mm W x 32 mm D)
Accesssories: 3.9kΩ End of Line Resistor; Wall Cover Plate (included); Surface Mount Electrical Box
Mounting: The module mounts directly to a 4-inch square electrical box with a minimum depth of 2 1/8 inches. For surface mounting, use 20-1346 surface mount box.
*The device supplies power through the supervisory line to the monitored devices.
P/N - Description
55-055 - Zone Interface Module, Non-isolator
55-060 - Zone Interface Module, Isolator
File Name: | fike-zone-interface-module-P.1.114.01-2.pdf |
Category: | Fike |
File Size: | |
File Type: | application/pdf |
Kunjungan: | 915 Kunjungan |
Download: | 135 kali |
Last Updated: | 17-06-2021 |
Cheetah XI 50 Intelligent Panel FM200 Suppression Control System
Horn Strobe Evacuation Conventional Signals Alarm Selectable Candela Fire Alarm System
Conventional Zone Module Fire Alarm System
FCP-300 Addressable Fire Alarm Control Communicator
Supervisory Control Module Fire Alarm System
CIE-A-200 Addressable Control Panel Fire Alarm System