SUPERVISORY CONTROL MODULE
DESCRIPTION
The Control Module, P/N 55-042 & 55-047, provides a means to switch an external power supply to notification appliances or release solenoids used for sprinkler operation, or to activate Fike’s Masterbox Interface module, P/N 10-2413, which is used on a Local Energy Type Auxiliary Fire Alarm System.
The module is capable of Class A or Class B wiring. The device will monitor the wiring (while external power is not switched to the auxiliary devices) to the connected device for open and short circuits via an end of line resistor (Class B only). The module will monitor the external power input for loss of power (DC voltage
supplies only). The isolator version of the module, P/N 55-047, provides complete short circuit isolation for installations requiring NFPA, Class X wiring.
The module is compatible with Fike’s CyberCat® and Cheetah® Xi intelligent control panels. Its operating parameters are configured using the panel’s programming software and are stored within non-volatile RAM in the module. This on-board intelligence allows each module to communicate its status directly to other devices connected to the panel. This peer-to-peer digital protocol results in less information that needs to be sent between the module and the host control panel, resulting in faster, more reliable communication.
APPROVALS
• UL - S2203
• FM
• City of New York - 8-05-E
• CSFM - 7165-0900:0137
SPECIFICATIONS
Normal Operating Voltage: 15 to 30 VDC
Standby Current: 630 uA max. average (continuous broadcasts)
Alarm Current: 2 mA (red LED on)
Maximum NAC Circuit Line Loss: 4 VDC
Power Supply Monitor: Regulated 24 VDC
Trouble Range: 0 to 2 VDC
Temperature Range: 32 to 120°F (0 to 49°C)
Humidity: 10 to 93% RH Non-condensing
Dimensions: 4.675”H x 4.275”W x 1.4”D
(119 mm H x 109 mm W x 36 mm D)
Accessories: 39kΩ End of Line Resistor P/N 10-2625 (included)
Wall cover plate (included)
Surface Mount Electrical Box: P/N 20-1347
Control Module Barrier: P/N 20-1346
Series Solenoid Diode/Resistor: P/N 10-2360
Mounting: Mounts directly on a 4-inch square electrical box with a minimum depth of 2 1/8 inches. For surface mounting, use 20-1347 surface mount box.
ORDERING INFORMATION
Fike P/N
55-042 Supervised Control Module - Non-isolator
55-047 Supervised Control Module - Isolator
Accessories
20-1346 Control Module Barrier
20-1347 Surface Mount Box
55-051 IR Tool
10-2360 Series Solenoid Diode/Resistor
10-2625 39K EOL
13-0192 COVERPLATE
File Name: | fike-supervisory-control-module-P.1.94.01-4-output-module.pdf |
Category: | Fike |
File Size: | |
File Type: | application/pdf |
Kunjungan: | 1150 Kunjungan |
Download: | 148 kali |
Last Updated: | 17-06-2021 |
135°/190° Rate of Rise Thermal Temperature Fix Heat Detector Conventional Fire Alarm System
Horn Strobe Evacuation Conventional Signals Alarm Selectable Candela Fire Alarm System
FCP-300 Addressable Fire Alarm Control Communicator
Cheetah XI 50 Intelligent Panel FM200 Suppression Control System
CIE-A-200 Addressable Control Panel Fire Alarm System
Photoelectric Smoke Detector Conventional