230 Downloads
GAQF.EX5054 - Clean Agent Extinguishing System Units
Clean Agent Extinguishing System Units
See General Information for Clean-agent Extinguishing System Units
KIDDE FIRE PROTECTION
1st Floor, Stokenchurch House
Oxford Road
High Wycombe
Stokenchurch, Buckinghamshire HP14 3SX
UNITED KINGDOM
ENGINEERED UNITS
Models E7763-101, E7763-102, E7763-103, E7763-104, E7763-105, E7763-106, E7763-107, E7763-108, E7763-109, E7763-110, E7763-111, E7763-112, and E7763-113, GX-20 Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 5, 8, 16, 28, 51, 81, 81, 142, 142, 243, 243, 368 and 368 liters of FM-200 Clean Agent, respectively. The units are super-pressurized to 25 bar with operating temperatures of -0 C to +54 C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
These systems are intended to be designed and installed in accordance with the Listee's Design, Installation, Operation and Maintenance Manual, P/N 59812-422, Issue C, dated November 2004. These installations require the use of the Listee's Flow Calculation Software, Version GX3.03 (reference Software User's Manual P/N E9832-014, Issue B, dated November 2004). Copies are available from the Listee.
Last Updated on 2015-04-22.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright noticein the following format: "© 2021 UL LLC"
File Name: | kidde-fire-protection-ul-certificate-GAQF.EX5054-clean-agent-extinguishing-system-units.pdf |
Category: | Kidde Fire Systems |
File Size: | |
File Type: | application/pdf |
Kunjungan: | 1034 Kunjungan |
Download: | 230 kali |
Last Updated: | 14-05-2021 |
UL Underwriters Laboratories, Inc. Certificate - GOYW.EX4674 Clean Agent Extinguishing System Units, Marine.
UL Underwriters Laboratories, Inc. Certificate - GOYWC.EX4674 Clean Agent Extinguishing System Units, Marine.
Kidde-Fenwal, Inc. Total Flooding Clean Agent FM-200 Engineered Fire Suppression System, Marine ECS Series. Machinery Space, Cargo Pump Rooms & Other Enclosed Spaces.
UL Underwriters Laboratories, Inc. Certificate - GAQF.EX4674 Clean Agent Extinguishing System Units.
DNV GL Certificate Kidde Fire Systems Marine ECS HFC-227ea Fire Suppression System - Equivalent Fixed Gas Fire Extinguishing System. Approved for use as "total flooding" fire extinguishing system in machinery spaces and cargo pump rooms.