153 Downloads
DNV-GL
Certificate No: TAF00000NA
TYPE APPROVAL CERTIFICATE
This is to certify:
That the Equivalent Fixed Gas Fire Extinguishing System
with type designation(s)
Kidde Fire Systems Marine ECS HFC-227ea Fire Suppression System
Issued to
Kidde-Fenwal
ASHLAND MA, United States
is found to comply with
DNV GL statutory interpretations DNVGL-SI-0364 – SOLAS interpretations
DNV GL rules for classification – Ships
DNV GL offshore standards
Application:
Approved for use as "total flooding" fire extinguishing system in machinery spaces and cargo pump rooms.
Minimum design gas concentration: 8.7%
Product(s) approved by this certificate is/are accepted for installation on all vessels classed by DNV GL.
Issued at Høvik on 2017-06-23
This Certificate is valid until: 2022-06-22.
DNV GL local station: New York
Approval Engineer: Fryderyk Hoga
Product description
“Kidde Fire Systems Marine ECS HFC-227ea Fire Suppression System”
is an equivalent fixed gas fire extinguishing system composed of gas cylinders with associated cylinder valves, flexible hoses, manifold, section valves, alarms, time delay units, piping and discharge nozzles.
The extinguishing concentration and the nozzles are covered by this type approval certificate. Other
components submitted for this type approval are reviewed, but shall be submitted and approved for each project. The system is to be designed in accordance with IMO MSC/Circ.848 as amended by IMO MSC.1/Circ.1267.
The gas is produced by Chemours, Wilmington, DE, USA.
Kidde Fire Systems Marine ECS HFC-227ea Fire Suppression System physical properties:
1) To be applied in conjunction with IMO MSC/Circ.848, 3.4.2.3.2
2) When calculated at 20°C. Ambient temperature to be determined case by case for each project
3) NFPA 2001 (2008 Edition)
Application/Limitation
The design gas concentration (diesel) shall be minimum 8.7% (applied on a net volume) and the maximum agent discharge time shall be 10 seconds.
The extinguishing system shall be designed and installed according to SOLAS Ch. II-2, IMO MSC/Circ.848 as amended by IMO MSC.1/Circ.1267 and the Kidde manual.
The following additional limitations will apply:
The following documentation is to be submitted to the flag administration in each separate case:
1. Plans showing location of cylinders, piping, nozzles and release stations as well as the assembled system.
2. Capacity calculations, including hydraulic flow calculations.
3. Plans defining release lines and alarm system.
4. Material specification and dimensions for piping and specifications for all other components.
5. Ship specific release procedures and post discharge ventilation procedures.
6. Manual containing design, inspection, operation and maintenance procedures.
7. Control arrangements for closure of openings and stop of fans and any pressure relief devices as per IMO MSC/Circ. 848, 13. These plans can also be supplied by yard.
Testing at installations and periodical surveys
- The system shall be tested as per maker’s manual both at installations and at periodical surveys, except that DNV do not require monthly content check of cylinders.The test pressure is minimum 53 bar for any closed sections, whereas open section shall be tightness tested at minimum 7 bar.
- The system is subject to biennial (every 2nd year) inspections by a DNV approved service supplier. The attending surveyor will also apply the DNV Instructions to Surveyors on newbuilding and ship in operation surveys.
Type Approval documentation
Certification in accordance with Class Programme DNVGL-CP-0338, October 2015.
Design, Installation, Operation and Maintenance Manual – P/N 06-236225-001, issued October 2014 from Kidde Fire Systems.
Report No. CG-D-24-97 dated October 1997 from USCG Research and Development Centre, Connecticut, USA.
Report No. CG-D-02-99 dated December 1998 from USCG Research and Development Centre, Connecticut, USA.
Tests carried out
Tested in accordance with IMO MSC/Circ.776 (IMO MSC/Circ.848) as amended by IMO MSC.1/Circ.1267.
Marking of product
Main components in the system are to be marked with name of manufacturer and type designation.
Periodical assessment
DNV GL’s surveyor is to be given permission to perform Periodical Assessments at any time during the validity of this certificate and at least every second year. The arrangement is to be in accordance with procedure described in Class Programme DNVGL-CP-0338, Section 4.
This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
File Name: | kidde-fire-systems-det-norske-veritas-dnv-gl-TAF00000NA-type-approval-certificate-marine-ecs-fm200-fire-suppression-system.pdf |
Category: | Kidde Fire Systems |
File Size: | |
File Type: | application/pdf |
Kunjungan: | 777 Kunjungan |
Download: | 153 kali |
Last Updated: | 14-05-2021 |
UL Underwriters Laboratories, Inc. Certificate - GAQF.EX5054 Clean Agent Extinguishing System Units.
U.S. Coast Guard Certification - Kidde-Fenwal, Inc. HFC-227ea total flooding clean agent fixed fire extinguishing systems. ECS series systems for the protection of machinery spaces, cargo pump rooms, and other enclosed spaces.
Kidde Fenwal, Inc - American Bureau of Shipping [ABS] 11-HS776659-1-PDA - Confirmation of Product Type Approval FM200 ADS Series Engineered Fire Suppression System
Kidde-Fenwal, Inc. Total Flooding Clean Agent FM-200 Engineered Fire Suppression System, Marine ECS Series. Machinery Space, Cargo Pump Rooms & Other Enclosed Spaces.