GAQFC.EX4674 - Clean Agent Extinguishing System Units
Clean Agent Extinguishing System Units
Kidde-Fenwal Inc
400 Main St
Ashland, MA 01721-2150
United States
Pre-Engineered Type
Kidde and Fenwal HFC-227ea extinguishing system [4.5 to 227 kg capacity] designed to discharge HFC-227ea extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Suitable for use in occupied or unoccupied areas at temperatures from 0°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, and the manufacturer's design manual.
Each system includes as a minimum - cylinder, mounting bracket, and valve assemblies as shown in the following table:
Nom Size | Fill Range | Kidde Part | Fenwal Part | Valve Size | |
[kg] | [kg] | [No.] | [No.] | [mm] | [NPS] |
4.5 | 2.7 - 4.5 | 90-100010-001 | 93-100010-001 | 38 | [1-1/2] |
4.5 | 2.7 - 4.5 | 90-100011-001 | 93-100011-001 | 38 | [1-1/2] |
9.0 | 5.0 - 9.0 | 90-100020-001 | 93-100020-001 | 38 | [1-1/2] |
9.0 | 5.0 - 9.0 | 90-100021-001 | 93-100021-001 | 38 | [1-1/2] |
18.0 | 9.5 - 18.0 | 90-100040-001 | 93-100040-001 | 38 | [1-1/2] |
18.0 | 9.5 - 18.0 | 90-100041-001 | 93-100041-001 | 38 | [1-1/2] |
32.0 | 18.6 - 32.0 | 90-100070-001 | 93-100070-001 | 38 | [1-1/2] |
32.0 | 18.6 - 32.0 | 90-100071-001 | 93-100071-001 | 38 | [1-1/2] |
57.0 | 32.0 - 57.0 | 90-100121-001 | 93-100121-001 | 38 | [1-1/2] |
57.0 | 32.0 - 57.0 | 90-100125-001 | 93-100125-001 | 38 | [1-1/2] |
91.0 | 57.0 - 91.0 | 90-1000200-001 | 93-100200-001 | 50 | [2] |
91.0 | 57.0 - 91.0 | 90-1000200-101 | 93-100200-101 | 50 | [2] |
91.0 | 57.0 - 91.0 | 90-100201-001 | 93-100201-001 | 50 | [2] |
91.0 | 57.0 - 91.0 | 90-100201-101 | 93-100201-101 | 50 | [2] |
159.0 | 91.0 - 159.0 | 90-100350-001 | 93-100350-001 | 50 | [2] |
159.0 | 91.0 - 159.0 | 90-100351-001 | 93-100351-001 | 50 | [2] |
227.0 | 159.0 - 227.0 | 90-100600-001 | 93-100600-001 | 64 | [3] |
227.0 | 159.0 - 227.0 | 90-100601-001 | 93-100601-001 | 64 | [3] |
272.0 | 117.0 - 272.0 | 90-100600-100 | 93-100600-100 | 76 | [3] |
272.0 | 117.0 - 272.0 | 90-100601-100 | 93-100601-100 | 76 | [3] |
408.0 | 178.0 - 408.0 | 90-100900-001 | 93-100900-001 | 76 | [3] |
408.0 | 178.0 - 408.0 | 90-100901-001 | 93-100901-001 | 76 | [3] |
Kidde and Fenwal HFC-227ea extinguishing system designed to discharge HFC-227ea extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Suitable for use in occupied or unoccupied areas at temperatures from 0°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, and the manufacturer's design manual, and flow calculation software versions KID 4.00 [Kidde brands] and FEN 4.00 [Fenwal brands].
Engineered Type
Each system includes as a minimum - cylinder, mounting bracket, and valve assemblies as shown in the following table:
Nom Size [kg] | Fill Range [kg] | Kidde Part No. | Fenwal Part No. | Valve Size [mm] |
4.5 | 2.27 - 4.5 | 90-100010-001 | 93-100010-001 | 38 |
4.5 | 2.27 - 4.5 | 90-100011-001 | 93-100011-001 | 38 |
9.0 | 4.0 - 9.0 | 90-100020-001 | 93-100020-001 | 38 |
9.0 | 4.0 - 9.0 | 90-100021-001 | 93-100021-001 | 38 |
18.0 | 7.7 - 18.0 | 90-100040-001 | 93-100040-001 | 38 |
18.0 | 7.7 - 18.0 | 90-100041-001 | 93-100041-001 | 38 |
32.0 | 13.7 - 32.0 | 90-100070-001 | 93-100070-001 | 38 |
32.0 | 13.7 - 32.0 | 90-100071-001 | 93-100071-001 | 38 |
57.0 | 24.5 - 57.0 | 90-100121-001 | 93-100121-001 | 38 |
57.0 | 24.5 - 57.0 | 90-100125-001 | 93-100125-001 | 38 |
91.0 | 39.0 - 91.0 | 90-100200-001 | 93-100200-001 | 50 |
91.0 | 39.0 - 91.0 | 90-100201-001 | 93-100201-001 | 50 |
91.0 | 39.0 - 91.0 | 90-100200-101 | 93-100200-101 | 50 |
91.0 | 39.0 - 91.0 | 90-100201-101 | 93-100201-101 | 50 |
159.0 | 68.0 - 159.0 | 90-100350-001 | 93-100350-001 | 50 |
159.0 | 68.0 - 159.0 | 90-100351-001 | 93-100351-001 | 50 |
204.0 | 118.0-204.0 | 90-100451-001 | — | 50 |
272.0 | 117.0 - 272.0 | 90-100600-001 | 93-100600-001 | 64 |
272.0 | 117.0 - 272.0 | 90-100601-001 | 93-100601-001 | 64 |
272.0 | 117.0 - 272.0 | 90-100600-100 | 93-100600-100 | 76 |
272.0 | 117.0 - 272.0 | 90-100601-100 | 93-100601-100 | 76 |
408.0 | 178.0 - 408.0 | 90-100900-001 | 93-100900-001 | 76 |
408.0 | 178.0 - 408.0 | 90-100901-001 | 93-100901-001 | 76 |
Installation Manual:
Series ECS [9000], Part No. 06-236115-001 dated October 2014; Manual Supplement for Placement Supervision Part No. 06-236115-003 dated July 2016; Manual Supplement for Stainless Steel Nozzles Part No. 06-236115-004 dated May 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236115-005 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236115-006 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.
Series 9300, Part No. 06-236081-001 dated October 2014; Manual Supplement for Placement Supervision Part No. 06-236081-003 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017; and Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; Manual Addendum for Liquid Level Indicators, Part No. 06-236081-004 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.
Discharge Nozzles:
Size [mm] | Kidde 180° Nozzle Part No. |
Kidde 360° Nozzle Part No. |
Fenwal 180° Nozzle Part No. |
Fenwal 360° Nozzle Part No. |
13 | 90-194013-109 thru 172 | 90-194023-111 thru 185 | 93-194013-109 thru 172 | 93-194023-111 thru 185 |
19 | 90-194014-144 thru 228 | 90-194024-147 thru 238 | 93-194014-144 thru 228 | 93-194024-147 thru 238 |
25 | 90-194015-182 thru 290 | 90-194025-189 thru 313 | 93-194015-182 thru 290 | 93-194025-189 thru 313 |
32 | 90-194016-246 thru 386 | 90-194026-246 thru 404 | 93-194016-246 thru 386 | 93-194026-246 thru 404 |
38 | 90-194017-290 thru 438 | 90-194027-290 thru 469 | 93-194017-290 thru 438 | 93-194027-290 thru 469 |
50 | 90-194018-358 thru 578 | 90-194028-368 thru 609 | 93-194018-358 thru 578 | 93-194028-368 thru 609 |
Component | Part No. |
Initiator Assembly: | 31-199932-004, 31-199932-02 |
Flexible Discharge Hose: | 283898, 283899, 283900 |
Agent Release Module: | 895630, 895627, 897494, 897560 |
The following components may be added for variations of the basic system:
Component | Part No. |
Manifold Check Valves: | 877690, 878743 |
Check Valves: | 264985, 800327, 800266, 800443, 800444, 870152, 870151, 870100 |
Releasing Device [Alternate]: | A ULC labelled releasing device suitable for squib-operated discharge valves. |
Supervisory Pressure Switch: | 878709-01 |
Actuation Hose: | 264986, 264987, 85-264988-036 |
Pressure Operated Switch: | 486536, 981332 |
Pressure Operated Trip: | 874290 |
Mounting Brackets: | 486485, 486486, 486487, 486488 283945, 283934, 292971, 235317, 281866, 294651, 236125 |
Kidde ADS Series Engineered, Models 90-100225-001, 90-100221-001, 90-100395-001, 90-100391-001, 90-100501-001, 90-100675-001, 90-100671-001, 90-101010-001, 90-101011-001, HFC-227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 102, 102, 179, 179, 229, 307, 307, 459, 459 kg of HFC-227ea Clean Agent, respectively. The units have an operating temperature range of 0 °C to 54 °C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure. A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236068-001 dated October 2014; Manual Supplement for Placement Supervision, Part No. 06-236068-003 dated July 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for the Nozzle Part Number Consolidation., Part No. 06-237737-001 dated January 2020; and Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Nitrogen Driver Supervisory Pressure Switch Addendum Part No. 06-237707-001 dated August 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236068-004 dated June 2020; and Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236068-005 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.
Fenwal Phoenix Series Engineered, Models 93-100225-001, 93-100221-001, 93-100395-001, 93-100391-001, 93-100675-001, 93-100671-001, 93-101010-001, 93-101011-001, HFC-227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 102, 102, 179, 179, 307, 307, 459, 459 kg of HFC-227ea Clean Agent, respectively. The units have an operating temperature ranges of 0 °C to 54 °C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
The description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236069-001 dated October 2014; Manual Supplement for Placement Supervision, Part No. 06-236069-003 dated July 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018, Manual Addendum for the Nozzle Part Number Consolidation, Part No. 06-2360689-004, dated January 2020; and Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236069-005 dated June 2020; and Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.
These Installations require the use of the Listee's flow calculation software FEN Version 4.00 [reference flow calculation manual P/N 06-236129-001 dated March 2013]. Copies are available from the above Listee.
Engineered Type
Kidde Fire Systems and Fenwal Protection Systems Argonite [IG-55] extinguishing system designed to discharge argon/nitrogen extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Designed to be used in occupied and unoccupied areas at temperatures ranging from -29°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, the manufacturer's design manual for Kidde Fire Systems Engineered Fire Suppression Systems, Part No. 38-KFSARG-000, September, 2004, Manual Supplement for Placement Supervision Part No. 06-236432-002 dated December 2015, and Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017, and the Flow Calculations Software User's Manual, Part No. 38-KFSARG-100, December, 2004, or Fenwal Protection Systems Engineered Fire Suppression Systems, Part No. 38-FPSARG-000, September, 2004, and the Flow Calculations Software User's Manual, Part No. 38-FPSARG-100, September, 2004, both to be used with the Flow Calculation Software program.
These installations require the use of the Listee's Design and Flow Calculation Software, InertGas Flow Software Version 1.0.
Kidde Fire Systems Nitrogen [IG-100] extinguishing system designed to discharge nitrogen extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Designed to be used in occupied and unoccupied areas at temperatures ranging from -29°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, the manufacturer's design manual for Engineered Extinguishing Systems, Part No. 06-237459-001, October 2015, and Supplement for Placement Supervision, Part No. 06-237459-002, December 2015, and Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017, and the Flow Calculations Software User's Manual, Part No. 30000063, November 2003.
These installations require the use of the Listee's Design and Flow Calculation Software, Nitrogen Flow Calculation Software program Version 1.0.0.
Kidde Novec™ 1230™ Engineered Series, Models 45-100010-001, 45-100020-001, 45-100040-001, 45-100070-001, 45-100121-001, 45-100125-001, 45-100200-001, 45-100201-001, 45-100350-001, 45-100351-001, 45-100451-001, 45-100600-001, 45-100601-001, 45-100900-001, 45-100901-001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 4.5, 9.0, 18, 32, 57, 57, 91, 91, 159, 193, 159, 273, 273, 409, 409 kg of Novec™ 1230™ Clean Agent, respectively. The units are super-pressurized to 2480 kPa with operating temperatures of -18°C to 54°C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 45-N1230M-001 [alternate P/N 06-236553-001] dated April 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; and Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236553-006 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236553-009 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.
These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 45-N1230M-100, dated February 2005] or Version 4.0 [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 06-237379-001, dated July 2015]. Copies are available from the above Listee.
Fenwal Novec™ 1230™ Engineered Series, Models 44-100010-001, 44-100020-001, 44-100040-001, 44-100070-001, 44-100121-001, 44-100125-001, 44-100200-001, 44-100201-001, 44-100350-001, 44-100351-001, 44-100451-001, 44-100600-001, 44-100601-001, 44-100900-001, 44-100901-001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 4.5, 9.0, 18, 32, 57, 57, 91, 91, 159, 159, 193, 273, 273, 409, 409 kg of Novec™ 1230™ Clean Agent, respectively. The units are super-pressurized to 2480 kPa with operating temperatures of -18°C to 54°C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 44-NV1230-001 [alternate p/n 06-236554-001] September 2014; Manual Supplement for Nitrogen Pilot Bracket P/N 06-236554-003 dated January 2013; Manual Supplement for Placement Supervision, Part No. 06-236554-004 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236554-005 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.
These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference the User's Manual for Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44-NV1230-100, February 2005]. Copies are available from the above Listee.
Kidde ADS Series Engineered, Models 45-500201-001, 45-500351-001, 45-500451-001, 45-500601-001, and 45-500901-001 clean agent extinguishing system units, having nominal charging capacities of 200, 350, 450, 600, and 900 lbs 3M™ Novec™ 1230 Fire Protection Fluid [FK 5-1-12], respectively. The units are super-pressurized to 360 psig [25 bar] at 70°F [21°C] with operating temperatures of 32°F to 130°F [0°C to 54°C]. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
A description of these extinguishing system units and the design and installation limitations are contained in the Listee's Installation Manual Part No. 06-237256-001 dated July 2014; Manual Supplement for Placement Supervision Part No. 06-237256-005 dated July 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions Part No. 06-237553-001 dated August 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for Nozzle Part Number Consolidation Part No. 06.237737-001 dated January 2020; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Nitrogen Driver Supervisory Pressure Switch Addendum Part No. 06-237707-001 dated August 2020; and Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-237256-006 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-237256-007 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.
These installations require the use of the Listee's flow calculation software ADS Version 4.0 [reference flow calculation manual Part No. 06-237256-004 dated July 2014]. Copies of the software and manuals may be obtained from the above Listee.
Kidde Fire Systems ECS 500 psi Fire Suppression System with Novec 1230 Fire Protection Fluid, Models 45-550010-001, 45-550020-001, 45-550040-001, 45-550070-001, 45-550121-001, 45-550201-001, 45-550351-001, 45-550451-001, 45-550601-001, 45-550901-001, and 45-551101-001, Extinguishing System Units, stored pressure type having nominal charging capacities of 10, 20, 40, 70, 125, 200, 350, 450, 600, 900, and 1100 lb of Novec 1230 Fire Protection Fluid Clean Agent, respectively. The units are super-pressurized to 500 psig with operating temperatures of 32°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.
A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 06-237585-001 dated November 2019; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; and Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-237585-002 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-237585-003 dated August 2020; Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020; and Manual Addendum for 36” Actuation Hoses, Part No. 06-237585-004, dated January 2021.
These installations require the use of the Listee's Design and Flow Calculation Software, Version 4.0 [reference the User's Manual for Kidde FK-5-1-12 Design and Flow Calculation Software, P/N 06-237588-001, dated October 2017]. Copies are available from the above Listee.
Weight of Agent [lbs] | Part No. |
6-11 | 45-550010-001 |
12-23 | 45-550020-001 |
20-40 | 45-550040-001 |
35-70 | 45-550070-001 |
63-125 | 45-550121-001 |
63-125 | 45-550125-001 |
100-200 | 45-550200-001 |
100-200 | 45-550201-001 |
175-350 | 45-550350-001 |
175-350 | 45-550351-001 |
260-450 | 45-550451-001 |
300-600 | 45-550600-001 |
300-600 | 45-550601-001 |
455-910 | 45-550901-001 |
550-1099 | 45-551101-001 |
* Numeric version code, where X may be 0-9.
Last Updated on 2021-05-04
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications [files] must be presented in their entirety and in a nonmisleading manner, without any manipulation of the data [or drawings]. 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2021 UL LLC"
File Name: | kidde-fenwal-ul-certificate-GAQFC.EX4674-clean-agent-extinguishing-system-units.pdf |
Category: | Kidde Fire Systems |
File Size: | |
File Type: | application/pdf |
Kunjungan: | 925 Kunjungan |
Download: | 147 kali |
Last Updated: | 14-05-2021 |
U.S. Coast Guard Certification - Kidde-Fenwal, Inc. HFC-227ea total flooding clean agent fixed fire extinguishing systems. ECS series systems for the protection of machinery spaces, cargo pump rooms, and other enclosed spaces.
UL Underwriters Laboratories, Inc. Certificate - GAQF.EX4674 Clean Agent Extinguishing System Units.
EC Declaration of Conformity - Kidde Fire Systems Marine ECS HFC-227ea Fire Suppression System.
Kidde-Fenwal, Inc. Total Flooding Clean Agent FM-200 Engineered Fire Suppression System, Marine ECS Series. Machinery Space, Cargo Pump Rooms & Other Enclosed Spaces.
Kidde Fire Systems - FM Approvals Certificate ECS Fire Suppression System with HFC-227ea Agent.