Kidde-Fenwal, Inc - UL Certificate GAQFC.EX4674 Clean Agent Extinguishing System Units

144 Downloads

GAQFC.EX4674 - Clean Agent Extinguishing System Units
Clean Agent Extinguishing System Units

 

Kidde-Fenwal Inc
400 Main St
Ashland, MA 01721-2150
United States

 

Pre-Engineered Type

Kidde and Fenwal HFC-227ea extinguishing system [4.5 to 227 kg capacity] designed to discharge HFC-227ea extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Suitable for use in occupied or unoccupied areas at temperatures from 0°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, and the manufacturer's design manual.

Each system includes as a minimum - cylinder, mounting bracket, and valve assemblies as shown in the following table:

Nom Size Fill Range Kidde Part Fenwal Part Valve Size
[kg] [kg] [No.] [No.] [mm] [NPS]
4.5 2.7 - 4.5 90-100010-001 93-100010-001 38 [1-1/2]
4.5 2.7 - 4.5 90-100011-001 93-100011-001 38 [1-1/2]
9.0 5.0 - 9.0 90-100020-001 93-100020-001 38 [1-1/2]
9.0 5.0 - 9.0 90-100021-001 93-100021-001 38 [1-1/2]
18.0 9.5 - 18.0 90-100040-001 93-100040-001 38 [1-1/2]
18.0 9.5 - 18.0 90-100041-001 93-100041-001 38 [1-1/2]
32.0 18.6 - 32.0 90-100070-001 93-100070-001 38 [1-1/2]
32.0 18.6 - 32.0 90-100071-001 93-100071-001 38 [1-1/2]
57.0 32.0 - 57.0 90-100121-001 93-100121-001 38 [1-1/2]
57.0 32.0 - 57.0 90-100125-001 93-100125-001 38 [1-1/2]
91.0 57.0 - 91.0 90-1000200-001 93-100200-001 50 [2]
91.0 57.0 - 91.0 90-1000200-101 93-100200-101 50 [2]
91.0 57.0 - 91.0 90-100201-001 93-100201-001 50 [2]
91.0 57.0 - 91.0 90-100201-101 93-100201-101 50 [2]
159.0 91.0 - 159.0 90-100350-001 93-100350-001 50 [2]
159.0 91.0 - 159.0 90-100351-001 93-100351-001 50 [2]
227.0 159.0 - 227.0 90-100600-001 93-100600-001 64 [3]
227.0 159.0 - 227.0 90-100601-001 93-100601-001 64 [3]
272.0 117.0 - 272.0 90-100600-100 93-100600-100 76 [3]
272.0 117.0 - 272.0 90-100601-100 93-100601-100 76 [3]
408.0 178.0 - 408.0 90-100900-001 93-100900-001 76 [3]
408.0 178.0 - 408.0 90-100901-001 93-100901-001 76 [3]

 

Kidde and Fenwal HFC-227ea extinguishing system designed to discharge HFC-227ea extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Suitable for use in occupied or unoccupied areas at temperatures from 0°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, and the manufacturer's design manual, and flow calculation software versions KID 4.00 [Kidde brands] and FEN 4.00 [Fenwal brands].

 

Engineered Type

Each system includes as a minimum - cylinder, mounting bracket, and valve assemblies as shown in the following table:

Nom Size [kg] Fill Range [kg] Kidde Part No. Fenwal Part No. Valve Size [mm]
4.5 2.27 - 4.5 90-100010-001 93-100010-001 38
4.5 2.27 - 4.5 90-100011-001 93-100011-001 38
9.0 4.0 - 9.0 90-100020-001 93-100020-001 38
9.0 4.0 - 9.0 90-100021-001 93-100021-001 38
18.0 7.7 - 18.0 90-100040-001 93-100040-001 38
18.0 7.7 - 18.0 90-100041-001 93-100041-001 38
32.0 13.7 - 32.0 90-100070-001 93-100070-001 38
32.0 13.7 - 32.0 90-100071-001 93-100071-001 38
57.0 24.5 - 57.0 90-100121-001 93-100121-001 38
57.0 24.5 - 57.0 90-100125-001 93-100125-001 38
91.0 39.0 - 91.0 90-100200-001 93-100200-001 50
91.0 39.0 - 91.0 90-100201-001 93-100201-001 50
91.0 39.0 - 91.0 90-100200-101 93-100200-101 50
91.0 39.0 - 91.0 90-100201-101 93-100201-101 50
159.0 68.0 - 159.0 90-100350-001 93-100350-001 50
159.0 68.0 - 159.0 90-100351-001 93-100351-001 50
204.0 118.0-204.0 90-100451-001 50
272.0 117.0 - 272.0 90-100600-001 93-100600-001 64
272.0 117.0 - 272.0 90-100601-001 93-100601-001 64
272.0 117.0 - 272.0 90-100600-100 93-100600-100 76
272.0 117.0 - 272.0 90-100601-100 93-100601-100 76
408.0 178.0 - 408.0 90-100900-001 93-100900-001 76
408.0 178.0 - 408.0 90-100901-001 93-100901-001 76

 

Installation Manual:

Series ECS [9000], Part No. 06-236115-001 dated October 2014; Manual Supplement for Placement Supervision Part No. 06-236115-003 dated July 2016; Manual Supplement for Stainless Steel Nozzles Part No. 06-236115-004 dated May 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236115-005 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236115-006 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

Series 9300, Part No. 06-236081-001 dated October 2014; Manual Supplement for Placement Supervision Part No. 06-236081-003 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017; and Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; Manual Addendum for Liquid Level Indicators, Part No. 06-236081-004 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.

 

Discharge Nozzles:

Size [mm] Kidde 180° Nozzle
Part No.
Kidde 360° Nozzle
Part No.
Fenwal 180° Nozzle
Part No.
Fenwal 360° Nozzle
Part No.
13 90-194013-109 thru 172 90-194023-111 thru 185 93-194013-109 thru 172 93-194023-111 thru 185
19 90-194014-144 thru 228 90-194024-147 thru 238 93-194014-144 thru 228 93-194024-147 thru 238
25 90-194015-182 thru 290 90-194025-189 thru 313 93-194015-182 thru 290 93-194025-189 thru 313
32 90-194016-246 thru 386 90-194026-246 thru 404 93-194016-246 thru 386 93-194026-246 thru 404
38 90-194017-290 thru 438 90-194027-290 thru 469 93-194017-290 thru 438 93-194027-290 thru 469
50 90-194018-358 thru 578 90-194028-368 thru 609 93-194018-358 thru 578 93-194028-368 thru 609

 

Component Part No.
Initiator Assembly: 31-199932-004, 31-199932-02
Flexible Discharge Hose: 283898, 283899, 283900
Agent Release Module: 895630, 895627, 897494, 897560

 

The following components may be added for variations of the basic system:

Component Part No.
Manifold Check Valves: 877690, 878743
Check Valves: 264985, 800327, 800266, 800443, 800444, 870152, 870151, 870100
Releasing Device [Alternate]: A ULC labelled releasing device suitable for squib-operated discharge valves.
Supervisory Pressure Switch: 878709-01
Actuation Hose: 264986, 264987, 85-264988-036
Pressure Operated Switch: 486536, 981332
Pressure Operated Trip: 874290
Mounting Brackets: 486485, 486486, 486487, 486488
283945, 283934, 292971, 235317, 281866, 294651, 236125

 

Kidde ADS Series Engineered, Models 90-100225-001, 90-100221-001, 90-100395-001, 90-100391-001, 90-100501-001, 90-100675-001, 90-100671-001, 90-101010-001, 90-101011-001, HFC-227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 102, 102, 179, 179, 229, 307, 307, 459, 459 kg of HFC-227ea Clean Agent, respectively. The units have an operating temperature range of 0 °C to 54 °C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure. A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236068-001 dated October 2014; Manual Supplement for Placement Supervision, Part No. 06-236068-003 dated July 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for the Nozzle Part Number Consolidation., Part No. 06-237737-001 dated January 2020; and Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Nitrogen Driver Supervisory Pressure Switch Addendum Part No. 06-237707-001 dated August 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236068-004 dated June 2020; and Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236068-005 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

Fenwal Phoenix Series Engineered, Models 93-100225-001, 93-100221-001, 93-100395-001, 93-100391-001, 93-100675-001, 93-100671-001, 93-101010-001, 93-101011-001, HFC-227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 102, 102, 179, 179, 307, 307, 459, 459 kg of HFC-227ea Clean Agent, respectively. The units have an operating temperature ranges of 0 °C to 54 °C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

The description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236069-001 dated October 2014; Manual Supplement for Placement Supervision, Part No. 06-236069-003 dated July 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018, Manual Addendum for the Nozzle Part Number Consolidation, Part No. 06-2360689-004, dated January 2020; and Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236069-005 dated June 2020; and Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.

These Installations require the use of the Listee's flow calculation software FEN Version 4.00 [reference flow calculation manual P/N 06-236129-001 dated March 2013]. Copies are available from the above Listee.

 

Engineered Type

Kidde Fire Systems and Fenwal Protection Systems Argonite [IG-55] extinguishing system designed to discharge argon/nitrogen extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Designed to be used in occupied and unoccupied areas at temperatures ranging from -29°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, the manufacturer's design manual for Kidde Fire Systems Engineered Fire Suppression Systems, Part No. 38-KFSARG-000, September, 2004, Manual Supplement for Placement Supervision Part No. 06-236432-002 dated December 2015, and Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017, and the Flow Calculations Software User's Manual, Part No. 38-KFSARG-100, December, 2004, or Fenwal Protection Systems Engineered Fire Suppression Systems, Part No. 38-FPSARG-000, September, 2004, and the Flow Calculations Software User's Manual, Part No. 38-FPSARG-100, September, 2004, both to be used with the Flow Calculation Software program.

These installations require the use of the Listee's Design and Flow Calculation Software, InertGas Flow Software Version 1.0.

Kidde Fire Systems Nitrogen [IG-100] extinguishing system designed to discharge nitrogen extinguishing agent for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Designed to be used in occupied and unoccupied areas at temperatures ranging from -29°C to 54°C. Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent Fire Extinguishing Systems, NFPA 2001, the manufacturer's design manual for Engineered Extinguishing Systems, Part No. 06-237459-001, October 2015, and Supplement for Placement Supervision, Part No. 06-237459-002, December 2015, and Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017, and the Flow Calculations Software User's Manual, Part No. 30000063, November 2003.

These installations require the use of the Listee's Design and Flow Calculation Software, Nitrogen Flow Calculation Software program Version 1.0.0.

Kidde Novec™ 1230™ Engineered Series, Models 45-100010-001, 45-100020-001, 45-100040-001, 45-100070-001, 45-100121-001, 45-100125-001, 45-100200-001, 45-100201-001, 45-100350-001, 45-100351-001, 45-100451-001, 45-100600-001, 45-100601-001, 45-100900-001, 45-100901-001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 4.5, 9.0, 18, 32, 57, 57, 91, 91, 159, 193, 159, 273, 273, 409, 409 kg of Novec™ 1230™ Clean Agent, respectively. The units are super-pressurized to 2480 kPa with operating temperatures of -18°C to 54°C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 45-N1230M-001 [alternate P/N 06-236553-001] dated April 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; and Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236553-006 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236553-009 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 45-N1230M-100, dated February 2005] or Version 4.0 [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 06-237379-001, dated July 2015]. Copies are available from the above Listee.

Fenwal Novec™ 1230™ Engineered Series, Models 44-100010-001, 44-100020-001, 44-100040-001, 44-100070-001, 44-100121-001, 44-100125-001, 44-100200-001, 44-100201-001, 44-100350-001, 44-100351-001, 44-100451-001, 44-100600-001, 44-100601-001, 44-100900-001, 44-100901-001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 4.5, 9.0, 18, 32, 57, 57, 91, 91, 159, 159, 193, 273, 273, 409, 409 kg of Novec™ 1230™ Clean Agent, respectively. The units are super-pressurized to 2480 kPa with operating temperatures of -18°C to 54°C. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 44-NV1230-001 [alternate p/n 06-236554-001] September 2014; Manual Supplement for Nitrogen Pilot Bracket P/N 06-236554-003 dated January 2013; Manual Supplement for Placement Supervision, Part No. 06-236554-004 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236554-005 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference the User's Manual for Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44-NV1230-100, February 2005]. Copies are available from the above Listee.

Kidde ADS Series Engineered, Models 45-500201-001, 45-500351-001, 45-500451-001, 45-500601-001, and 45-500901-001 clean agent extinguishing system units, having nominal charging capacities of 200, 350, 450, 600, and 900 lbs 3M™ Novec™ 1230 Fire Protection Fluid [FK 5-1-12], respectively. The units are super-pressurized to 360 psig [25 bar] at 70°F [21°C] with operating temperatures of 32°F to 130°F [0°C to 54°C]. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's Installation Manual Part No. 06-237256-001 dated July 2014; Manual Supplement for Placement Supervision Part No. 06-237256-005 dated July 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions Part No. 06-237553-001 dated August 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for Nozzle Part Number Consolidation Part No. 06.237737-001 dated January 2020; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; Nitrogen Driver Supervisory Pressure Switch Addendum Part No. 06-237707-001 dated August 2020; and Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-237256-006 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-237256-007 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

These installations require the use of the Listee's flow calculation software ADS Version 4.0 [reference flow calculation manual Part No. 06-237256-004 dated July 2014]. Copies of the software and manuals may be obtained from the above Listee.

Kidde Fire Systems ECS 500 psi Fire Suppression System with Novec 1230 Fire Protection Fluid, Models 45-550010-001, 45-550020-001, 45-550040-001, 45-550070-001, 45-550121-001, 45-550201-001, 45-550351-001, 45-550451-001, 45-550601-001, 45-550901-001, and 45-551101-001, Extinguishing System Units, stored pressure type having nominal charging capacities of 10, 20, 40, 70, 125, 200, 350, 450, 600, 900, and 1100 lb of Novec 1230 Fire Protection Fluid Clean Agent, respectively. The units are super-pressurized to 500 psig with operating temperatures of 32°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 06-237585-001 dated November 2019; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for 1.5" and 2" flex discharge hoses, Part No. 06-237766-001 dated January 2020; and Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-237585-002 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-237585-003 dated August 2020; Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020; and Manual Addendum for 36” Actuation Hoses, Part No. 06-237585-004, dated January 2021.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 4.0 [reference the User's Manual for Kidde FK-5-1-12 Design and Flow Calculation Software, P/N 06-237588-001, dated October 2017]. Copies are available from the above Listee.

Weight of Agent [lbs] Part No.
6-11 45-550010-001
12-23 45-550020-001
20-40 45-550040-001
35-70 45-550070-001
63-125 45-550121-001
63-125 45-550125-001
100-200 45-550200-001
100-200 45-550201-001
175-350 45-550350-001
175-350 45-550351-001
260-450 45-550451-001
300-600 45-550600-001
300-600 45-550601-001
455-910 45-550901-001
550-1099 45-551101-001

* Numeric version code, where X may be 0-9.

Last Updated on 2021-05-04


The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications [files] must be presented in their entirety and in a nonmisleading manner, without any manipulation of the data [or drawings]. 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2021 UL LLC"

File Name: kidde-fenwal-ul-certificate-GAQFC.EX4674-clean-agent-extinguishing-system-units.pdf
Category: Kidde Fire Systems
File Size:
File Type: application/pdf
Kunjungan: 907 Kunjungan
Download: 144 kali
Last Updated: 14-05-2021

Dokumen Serupa

Kidde-Fenwal, Inc - US Coast Guard Certificate of Approval 162161_1 FM200 Total Flooding Clean Agent Fixed Fire Extinguishing Systems [Renewal]
Kidde-Fenwal, Inc - US Coast Guard Certificate of Approval 162161_1 FM200 Total Flooding Clean Agent Fixed Fire Extinguishing Systems [Renewal]

U.S. Coast Guard Certification - Kidde-Fenwal, Inc. HFC-227ea total flooding clean agent fixed fire extinguishing systems. ECS series systems for the protection of machinery spaces, cargo pump rooms, and other enclosed spaces.

Kidde Fire Protection - UL Certificate GAQF.EX5054 Clean Agent Extinguishing System Units
Kidde Fire Protection - UL Certificate GAQF.EX5054 Clean Agent Extinguishing System Units

UL Underwriters Laboratories, Inc. Certificate - GAQF.EX5054 Clean Agent Extinguishing System Units.

Kidde-Fenwal, Inc - UL Certificate GAQF.EX4674 Clean Agent Extinguishing System Units
Kidde-Fenwal, Inc - UL Certificate GAQF.EX4674 Clean Agent Extinguishing System Units

UL Underwriters Laboratories, Inc. Certificate - GAQF.EX4674 Clean Agent Extinguishing System Units.

Kunjungi Kami
alamat kantor ReedFOX Fire & Life Safety Indonesia
Padamin FM200 Fire Suppression System
Hubungi kami sekarang juga!
0813-1111-0220
small-logo.png
small-logo.png
Hubungi kami sekarang juga!
0813-1111-0220