• 0813-1111-0220
  • 0813-6111-6112
  • This email address is being protected from spambots. You need JavaScript enabled to view it.

Datasheet Produk

Kidde-Fenwal, Inc - UL Certificate GAQF.EX4674 Clean Agent Extinguishing System Units

183 Downloads

GAQF.EX4674 - Clean Agent Extinguishing System Units

Clean Agent Extinguishing System Units

 

Kidde-Fenwal Inc
400 Main St
Ashland, MA 01721-2150
United States

 

PRE-ENGINEERED, Fenwal Modular Spherical, Pre-Engineered, Models 93-120250-001, 93-120251-001, 93-120253-001, 93-120351-001, 93-120353-001, 93-110201-001, 93-110202-001, 93-110203-001, 93-110204-001, 93-192041-002, HFC-227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 15, 30, 30, 30, 30, 44, 63, 101, 130, 196, and 350 lbs., respectively. The units are super-pressurized with Nitrogen to 360 psig with operating temperatures of 32 to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual Part No. 06-236117-001 dated October 2014.

Kidde ECS Series Pre-Engineered, Models 90-100010-001, 90-100011-001, 90-100020-001, 90-100021-001, 90-100040-001, 90-100041-001, 90-100070-001, 90-100071-001, 90-100121-001, 90-100125-001, 90-100200-101, 90-100201-101, 90-100201-001, 90-100200-001, 90-100350-001, 90-100351-001, 90-100600-001, 90-100601-001 HFC-227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 10, 10, 20, 20, 40, 40, 70, 70, 125, 125, 200, 200, 200, 200, 350, 350, 500
and 500 lbs, respectively. The units are super-pressurized with Nitrogen to 360 psig with operating temperatures of 32 to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, Part No. 06-236116-001 dated October 2014; Manual Supplement for Placement Supervision, Part No. 06-236116-002 dated July 2016; Manual supplement for SS Nozzles, Part No. 06-236116-003 dated May 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018.; Manual Addendum for the use of a Main/Reserve Transfer Switch Part No. 06-236116-004 dated October 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for the 1.5" and 2" Flex Discharge Hoses, Addendum Part No. 06-237765-001 dated January 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

Fenwal 9300 Modular Pre-Engineered, Models 93-100010-001, 93-100011-001, 93-100020-001, 93-100021-001, 93-100040-001, 93-100041-001, 93-100070-001, 93-100071-001, 93-100121-001, 93-100125-001, 93-100200-101, 93-100201-101, 93-100201-001, 93-100200-001, 93-100350-001, 93-100351-001, 93-100600-001, 93-100601-001 HFC-227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 10, 10, 20, 20, 40, 40, 70, 70, 125, 125, 200, 200, 200, 200, 350, 350, 500
and 500 lbs, respectively. The units are super-pressurized with Nitrogen to 360 psig with operating temperatures of 32 to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, Part No. 06-236088-001 dated October 2014; Manual Supplement for Placement Supervision, Part No. 06-236088-002 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017; and Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018.

Kidde FE-13 Modular Pre-Engineered, Models 96-100065-001, 96-100112-001, HFC-23 Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 65, 112 lb of HFC-23 Clean Agent, respectively. The units have operating temperatures of -40 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 96-FE13MA-000 [06-236193-001] dated October 2002; Manual Supplement for Placement Supervision, Part No. 06-236116-002 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; and Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018.

ENGINEERED UNITS, Kidde ECS Series Engineered, Models 90-100010-001, 90-100020-001, 90-100040-001, 90-100070-001, 90-100121-001, 90-100125-001, 90-100200-001, 90100201-001, 90-100200-101, 90-100201-101,90-100350-001, 90-100351-001, 90-100451-001, 90-100600-001, 90-100601-001, 90100600-100, 90-100601-100, 90-100900-001, 90-100901-001, HFC-227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 10, 20, 40, 70, 125, 125, 200, 200, 200,
350, 350, 450, 600, 600, 600, 600, 900, 900 lb of HFC-227ea Clean Agent, respectively. The units are super-pressurized to 360 psig with operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236115-001 dated October 2014 along with Manual Supplement for Placement Supervision, Part No. 06-236115-003 dated July 2016; Manual Supplement for SS Nozzles, Part No. 06-236115-004 dated May 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670- 001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for the 1.5" and 2" Flex Discharge Hoses, Addendum Part No. 06-237765-001 dated January 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236115-005 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236115-006 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

These installations require the use of the Listee's flow calculation software KID Version 4.00. Copies are available from the above Listee.

Fenwal 9300 Series Engineered, Models 93-100010-001, 93-100020-001, 93-100040-001, 93-100070-001, 93-100121-001, 93-100125-001, 93-100200-001, 93-100200-101, 93-100201-101, 93-100350-001, 93-100351-001, 93-100600-001, 93-100601-001, 93-100600-100, 93-100601-100, 93-100900-001, 93-100901-001, HFC-227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 10, 20, 40, 70, 125, 125, 200, 200, 200, 350, 350, 600, 600, 600, 600, 900, 900 lb of HFC-227ea Clean Agent, respectively. The units are super-pressurized to 360 psig with operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236081-001 dated October 2014; Manual Supplement for Placement Supervision, P/N 06-236081-003 dated July 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; Manual Addendum for Liquid Level Indicators, Part No. 06-236081-004 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.

These installations require the use of the Listee's flow calculation software FEN Version 4.00. Copies are available from the above Listee.

Fenwal Sphere and Bottom Discharge Engineered, Models 93-120250-001, 93-120251-001, 93-120253-001, 93-120351-001, 93-120353-001, 93-110201-001, 93-110202-001, 93-110203-001, 93-110204-001, 93-192041-001, 93-192041-002, 93-192040-001, 93-192040-002, 93-192042-001, 93-192042-002, HFC-227ea Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 15, 30, 30, 30, 30, 44, 63, 101, 196, 350, 350, 560, 560, 850, 850 lb of HFC-227ea Clean Agent, respectively. The units are super-pressurized to 360 psig with operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual P/N 06-235879-001 dated October 2014, and Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017. These installations require the use of the Listee's flow calculation software FEN Version 4.00. Copies are available from the above Listee.

Kidde ADS Series Engineered, Models 90-100225-001, 90-100221-001, 90-100395-001, 90-100391-001, 90-100501-001, 90-100675-001, 90-100671-001, 90-101010-001, 90-101011-001 , HFC-227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 225, 225, 395, 395, 505, 675, 675, 1010, 1010 lb of HFC-227ea Clean Agent, respectively. The units have operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236068-001 dated October 2014 along with Manual Supplement for Placement Supervision, Part No. 06-236068-003 dated July 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018, ; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for the Nozzle Part Number Consolidation., Part No. 06-237737-001 dated January 2020; and Manual Addendum for the 1.5" and 2" Flex Discharge Hoses, Addendum Part No. 06-237765-001 dated January 2020; Nitrogen Driver Supervisory Pressure Switch Addendum
Part No. 06-237707-001 dated August 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236068-004 dated June 2020; and Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236068-005 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October
2020.

These installations require the use of the Listee's flow calculation software KID Version 4.00. Copies are available from the above Listee.

Fenwal Phoenix Series Engineered, Models 93-100225-001, 93-100221-001, 93-100395-001, 93-100391-001, 93-100675-001, 93-100671-001, 93-101010-001, 93-101011-001 HFC-227ea Clean Agent Extinguishing System Units, having nominal charging capacities of 225, 225, 395, 395, 675, 675, 1010, and 1010 lb of HFC-227ea Clean Agent, respectively. The units have operating temperatures of 32 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

The description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual, P/N 06-236069-001 dated October 2014; and Manual Supplement for Placement Supervision, Part No. 06-236069-003 dated July 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; and Manual Addendum for the Nozzle Part Number Consolidation, Part No. 06-2360689-004, dated January 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236069-005 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.

These Installations require the use of the Listee's flow calculation software FEN Version 4.00. Copies are available from the above Listee.

Engineered Clean Agent Extinguishing System Units containing HFC-227ea, stored pressure type utilizing IS 7285 cylinders, ECS Series Models 90-600080-001, 90-600080-100, 90-600200-001, 90-600300-001 and 90-600350-100 having nominal storage capacities of 34, 80, 120, and 140 L [80, 200, 300 and 350 lb] HFC-227ea clean agent. The units are super-pressurized with dry nitrogen to 360 psig [24.8 bar] at 70°F [21°C] with operating temperatures of 32°F to 130°F [0°C to 55°C]. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 06-237298-001 issued January 2020; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-501 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-501, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, KID Version 4.00. Copies are available from the above Listee.

Kidde FE-13 Engineered, Models 96-100065-001, 96-100112-001, HFC-23 Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 65, 112 lb of HFC-23 Clean Agent, respectively. The units have operating temperatures of -40 F to 130 F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual P/N 96-FE13MA-002 002 [06-236169-002] dated October 2002; Manual Supplement for Placement Supervision, Part No. 06-236169-003 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237615-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; and Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018.

These installations require the use of the Listee's flow calculation software KID Version 4.00. Copies are available from the above Listee.

Kidde Novec™ 1230™ Engineered Series, Models 45-100010-001, 45-100020-001, 45-100040-001, 45-100070-001, 45-100121-001, 45-100125-001, 45-100200-001, 45-100201-001, 45-100350-001, 45-100351-001, 45-100451-001, 45-100600-001, 45-100601-001, 45-100900-001, 45-100901-001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 10, 20, 40, 70, 125, 125, 200, 200, 350, 350, 425, 600, 600, 900, 900 lb of Novec™ 1230™ Clean Agent, respectively. The units are superpressurized to 360 psig with operating temperatures of 0°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 45-N1230M-001 alternate P/N 06-236553-001 dated April 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553- 001 dated August 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; and Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; and Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-236553-006 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-236553-009 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 45-N1230M-100, dated March 2006] or Version 4.0 [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 06-237379-001, dated July 2015]. Copies are available from the above Listee.

Kidde Novec™ 1230™ Engineered Series [EU Compliant], Models 45-990010-001, 45-990020-001, 45-990040-001, 45-990070-001, 45-990121-001, 45-990125-001, 45-990200-001, 45-990201-001, 45-990350-001, 45-990351-001, 45-990600-001, 45-990601-001, 45-990900-001, 45-990901-001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 10 [4.5], 20 [9.1], 40 [18.1], 70 [31.7], 125 [56.7], 125 [56.7], 200 [90.7], 200 [90.7], 350 [158.8], 350 [158.8], 600 [272.1], 600 [272.1], 900 [408.2], 900 [408.2] lb [kg] of Novec™ 1230™ Clean Agent, respectively. The units are super-pressurized to 360 psig with operating temperatures of 0°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 45-N1230M-001 [alternate P/N 06-236553-001] dated April 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553- 001 dated August 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018, ; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for the 1.5" and 2" Flex Discharge Hoses, Addendum Part No. 06-237765-001 dated January 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 45-N1230M-100, dated March 2006] or Version 4.0 [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 06-237379-001, dated July 2015]. Copies are available from the above Listee.

Fenwal Novec™ 1230™ Engineered Series, Models 44-100010-001, 44-100020-001, 44-100040-001, 44-100070-001, 44-100121-001, 44-100125-001, 44-100200-001, 44-100201-001, 44-100350-001, 44-100351-001, 44-100451-001, 44-100600-001, 44-100601-001, 44-100900-001, 44-100901-001 Clean Agent Extinguishing System Units, stored pressure type having nominal charging capacities of 10, 20, 40, 70, 125, 125, 200, 200, 350, 350, 425, 600, 600, 900, 900 lb of Novec™ 1230™ Clean Agent, respectively. The units are superpressurized to 360 psig with operating temperatures of 0°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 44-NV1230-001 [alternate P/N 06-236554-001] September 2014; Manual Supplement for Nitrogen Pilot Bracket P/N 06-236554-003 dated January 2013; Manual Supplement for Placement Supervision P/N 06-236554-004 dated July 2016; and Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; Manual Addendum for Liquid Level Indicators, Part No. 06-236554-005 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237786-001 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference the User's Manual for Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44-NV1230-100, February 2005]. Copies are available from the above Listee.

Fenwal Novec™ 1230™ Sphere and Bottom Discharge Engineered Series, Models 44-120250-001, 44-120251-001, 44-110201-001, 44-110202-001, 44-110203-001, 44-110204-001, 44-192041-001, 44-192041-002, 44-192040-001, 93-192040-002, 44-192042-001, 44-192042-002, Clean Agent Extinguishing System Units, stored pressure type , having nominal charging capacities of 15, 30, 44, 63, 101, 196, 350, 350, 560, 560, 850, 850 lb of Novec™ 1230™ Clean Agent, respectively. The units are super-pressurized to 360 psig with operating temperatures of 0°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 44-NV1230-001 [alternate P/N 06-236554-001] September 2014; Manual Supplement for Nitrogen Pilot Bracket P/N 06-236554-003 dated January 2013; Manual Supplement for Placement Supervision, Part No. 06-236554-004 dated July 2016; Manual Addendum for Class B Minimum Design concentrations, Part No. 06-237624-001 dated August 2017; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237578-001 dated May 2018; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237799-001, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference User's Manual for Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44-NV1230-100, February 2005]. Copies are available from the above Listee.

Engineered Clean Agent Extinguishing System Units containing 3M Novec 1230 Fire Protection Fluid [FK-5-1-12], stored pressure type utilizing IS 7285 cylinders, ECS Series Models 45-600080-001, 45-600080-100, 45-600200-001, 45-600300-001 and 45-600350-001 having nominal storage capacities of 34, 80, 120 and 140 L of Novec 1230 Fluid [FK-5-1-12]. The units are super-pressurized with dry nitrogen to 360 psig [24.8 bar] at 70°F [21°C] with operating temperatures of 0°F to 130°F [-18°C to 55°C]. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N P/N 06-237127-600 issued January 2020; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-501 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-501, dated October 2020.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 1.0.X* [reference User's Manual for Fenwal Novec 1230 Design and Flow Calculation Software, P/N 44-NV1230-100, February 2005] or Version 4.0 [reference the User's Manual for Kidde Novec 1230 Design and Flow Calculation Software, P/N 06-237369-001, dated July 2015]. Copies are available from the above Listee.

Kidde ADS Series Engineered, Models 45-500201-001, 45-500351-001, 45-500451-001, 45-500601-001, and 45-500901-001 clean agent extinguishing system units, having nominal charging capacities of 200, 350, 450, 600, and 900 lbs 3M™ Novec™ 1230 Fire Protection Fluid [FK 5-1-12], respectively. The units are super-pressurized to 360 psig [25 bar] at 70°F [21°C] with operating temperatures of 32°F to 130°F [0°C to 54°C]. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's Installation Manual, Part No. 06-237256-001 dated July 2014; Manual Supplement for Placement Supervision, Part No. 06-237256-005 dated July 2016; Manual addendum for 2" Valve and Safety Burst Disc Rebuild Kit and Instructions, Part No. 06-237553-001 dated August 2016; Manual Addendum for the new lever and pressure operated control head assemblies, Part No. 06-237577-001 dated May 2018; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for Nozzle Part Number Consolidation Part No. 06.237737-001 dated January 2020; Manual Addendum for the 1.5" and 2" Flex Discharge Hoses, Addendum Part No. 06-237765-001 dated January 2020; Nitrogen Driver Supervisory Pressure Switch Addendum Part No. 06-237707-001 dated August 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-237256-006 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; and Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-237256-007 dated August 2020; and Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020.

These installations require the use of the Listee's flow calculation software ADS Version 4.0 [reference flow calculation manual Part No. 06-237256-004 dated July 2014]. Copies of the software and manuals may be obtained from the above Listee.

Kidde Fire Systems ECS 500 psi Fire Suppression System with Novec 1230 Fire Protection Fluid, Models 45-550010-001, 45-550020-001, 45-550040-001, 45-550070-001, 45-550121-001, 45-550201-001, 45-550351-001, 45-550451-001, 45-550601-001, 45-550901-001, and 45-551101-001, Extinguishing System Units, stored pressure type having nominal charging capacities of 10, 20, 40, 70, 125, 200, 350, 450, 600, 900, and 1100 lb of Novec 1230 Fire Protection Fluid Clean Agent, respectively. The units are super-pressurized to 500 psig with operating temperatures of 32°F to 130°F. The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations, are contained in the Listee's Design, Installation, Operation and Maintenance Manual, P/N 06-237585-001, dated November 2019; Manual Addendum for the placement of Warning Signs in the protected enclosure, Part No. 06-237670-001 dated December 2018; Manual Addendum for Installation of Control Head Monitor, Part No. 06-237750-001 dated November 2019; Manual Addendum for the 1.5" and 2" Flex Discharge Hoses, Addendum Part No. 06-237765-001 dated January 2020; Manual Addendum for Main-to-Reserve Transfer Switch, Part No. 06-237781-001 dated August 2020; Manual Addendum for Liquid Level Indicators, Part No. 06-237585-002 dated June 2020; Manual Addendum for 2" and 3" Valve Burst Disc Harmonization, Part No. 06-237783-001 dated August 2020; Manual Addendum for 450-lb Cylinder Assemblies, Part No. 06-237585-003 dated August 2020; Manual Addendum for 2 Inch El-Check Valve, Part No. 06-237797-001, dated October 2020; and Manual Addendum for 36” Actuation Hoses, Part No. 06-237585-004, dated January 2021.

These installations require the use of the Listee's Design and Flow Calculation Software, Version 4.0 [reference the User's Manual for Kidde FK-5-1-12 Design and Flow Calculation Software, P/N 06-237588-001, dated October 2017]. Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY
Weight of Agent [lbs] Part No.
6-11 45-550010-001
12-23 45-550020-001
20-40 45-550040-001
35-70 45-550070-001
63-125 45-550121-001
63-125 45-550125-001
100-200 45-550200-001
100-200 45-550201-001
175-350 45-550350-001
175-350 45-550351-001
260-450 45-550451-001
300-600 45-550600-001
300-600 45-550601-001
455-910 45-550901-001
550-1099 45-551101-001

* Numeric version code, where X may be 0-9.

Last Updated on 2021-05-04


The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications [files] must be presented in their entirety and in a non-misleading manner, without any manipulation of the data [or drawings]. 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2021 UL LLC"

File Name: kidde-fenwal-ul-certificate-GAQF.EX4674-clean-agent-extinguishing-system-units.pdf
Category: Kidde Fire Systems
File Size:
File Type: application/pdf
Kunjungan: 2123 Kunjungan
Download: 183 kali
Last Updated: 14-05-2021

Dokumen Serupa

Kidde-Fenwal - Det Norske Veritas [DNV GL] F-20253 - Type Approval Certificate Approved for Use as Total Flooding Fire Extinguishing System in Machinery Spaces and Cargo Pump Rooms - Minimum Design Gas Concentration 8.7%
Kidde-Fenwal - Det Norske Veritas [DNV GL] F-20253 - Type Approval Certificate Approved for Use as Total Flooding Fire Extinguishing System in Machinery Spaces and Cargo Pump Rooms - Minimum Design Gas Concentration 8.7%

U.S. Coast Guard Certificate Kidde-Fenwal, Inc - HFC-227ea total flooding clean agent fixed fire extinguishing systems. ECS series systems for the protection of machinery spaces, cargo pump rooms, and other enclosed spaces.

Kidde-Fenwal, Inc - US Coast Guard Certificate of Approval 162161_7 FM200 Total Flooding Clean Agent Fixed Fire Extinguishing Systems [Renewal]
Kidde-Fenwal, Inc - US Coast Guard Certificate of Approval 162161_7 FM200 Total Flooding Clean Agent Fixed Fire Extinguishing Systems [Renewal]

U.S. Coast Guard Certification - Kidde-Fenwal, Inc. HFC-227ea total flooding clean agent fixed fire extinguishing systems. ECS series systems for the protection of machinery spaces, cargo pump rooms, and other enclosed spaces.

Kidde-Fenwal - American Bureau of Shipping [ABS] 03-HS357143-3-PDA - Confirmation of Product Type Approval FM200 Engineered Fire Suppression System, Marine ECS Series
Kidde-Fenwal - American Bureau of Shipping [ABS] 03-HS357143-3-PDA - Confirmation of Product Type Approval FM200 Engineered Fire Suppression System, Marine ECS Series

Kidde-Fenwal, Inc. Total Flooding Clean Agent FM-200 Engineered Fire Suppression System, Marine ECS Series. Machinery Space, Cargo Pump Rooms & Other Enclosed Spaces.

Kidde-Fenwal, Inc - UL Certificate GAQFC.EX4674 Clean Agent Extinguishing System Units
Kidde-Fenwal, Inc - UL Certificate GAQFC.EX4674 Clean Agent Extinguishing System Units

UL Underwriters Laboratories, Inc. Certificate - GAQFC.EX4674 Clean Agent Extinguishing System Units.

Kidde-Fenwal, Inc - UL Certificate GOYW.EX4674 Clean Agent Extinguishing System Units, Marine
Kidde-Fenwal, Inc - UL Certificate GOYW.EX4674 Clean Agent Extinguishing System Units, Marine

UL Underwriters Laboratories, Inc. Certificate - GOYW.EX4674 Clean Agent Extinguishing System Units, Marine.

Kidde Fire Systems FM200 EC Declaration of Conformity EC Type Examination Certificate MEDB00002NR
Kidde Fire Systems FM200 EC Declaration of Conformity EC Type Examination Certificate MEDB00002NR

EC Declaration of Conformity - Kidde Fire Systems Marine ECS HFC-227ea Fire Suppression System.

Kunjungi Kami
alamat kantor ReedFOX Fire & Life Safety Indonesia
Padamin FM200 Fire Suppression System
Hubungi kami sekarang juga!
0813-1111-0220
small-logo.png
small-logo.png
Hubungi kami sekarang juga!
0813-1111-0220